Index termination, Index termination -48 – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual
Page 64

Publication 2098-RM003A-EN-P October 2001
2-48
Command Reference
Index Termination
Format:
:aa0B6fnnddcc<cr>
Parameter
Code:
0x0B6
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
0xA = Read Minimum Array Index Value
0xB = Read Maximum Array Index Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x07 = Invalid Array Index
0x08 = Invalid Function Code
Data Fields:
nn
Array index
dd
Index termination for the specified index, where:
0x00: Stop
0x01: Start another immediately
0x02: Start another w/start index input
0x03: Start another index without stopping.
Minimum
Value:
0x00
Maximum
Value:
0x02
Minimum Array
Index Value:
0x00
Maximum Array
Index Value:
0x3F
Default:
0x00