Motor rated voltage, Motor rated voltage -82 – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual
Page 98
Advertising
![background image](/manuals/580675/98/background.png)
Publication 2098-RM003A-EN-P October 2001
2-82
Command Reference
Motor Rated Voltage
Format:
:aa0ECfddddcc<cr>
Parameter
Code:
0x0EC
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields:
dddd
Rated voltage of the motor, in units of AC RMS
Volts.
Minimum
Value:
100
Maximum
Value:
1000
Default:
230