Publication 2098-RM003A-EN-P October 2001

2-16

Command Reference

Machine Cycle Size

Position Rollover Enable/Disable

Format:

:aa193fddddddddcc<cr>

Parameter
Code:

0x193

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddddddd

Machine cycle rollover position, in units of counts.

Minimum
Value:

0x00000064

Maximum
Value:

0x7FFFFFFF

Default:

0x7FFFFFFF

Format:

:aa194fddcc<cr>

Parameter
Code:

0x194

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dd

Enables or disables the rollover of position variables
according to the machine cycle size parameter.

Minimum
Value:

0x00

Maximum
Value:

0x01

Default:

0x01