Publication 2098-RM003A-EN-P October 2001
Command Reference
2-19
Broadcast Address
Reset Serial Port
Format:
:aa053fddcc<cr>
Parameter
Code:
0x053
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x08 = Invalid Function Code
Data Fields:
dd
Broadcast address for serial communications.
Default:
0xFF
Format:
:aa10Afcc<cr>
Parameter
Code:
0x10A
Valid Function
Codes:
0x1 = Write Working Value
Valid Exception
Codes:
0x06 = Command Disabled when Drive is Enabled
0x08 = Invalid Function Code
Data Fields:
None