Communications commands, Baud rate, Communications commands -17 – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual

Page 33: Baud rate -17

Advertising
background image

Publication 2098-RM003A-EN-P October 2001

Command Reference

2-17

Communications
Commands

Baud Rate

Format:

:aa050fddcc<cr>

Parameter
Code:

0x050

Valid Function
Codes:

0x0 = Read Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dd

Baud rate code, where:
0x00: 1200 baud
0x01: 2400 baud
0x02: 4800 baud
0x03: 9600 baud
0x04: 19200 baud
0x05: 38400 baud

Minimum
Value:

0x00

Maximum
Value:

0x05

Default:

0x05