Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 102

Advertising
background image

5-4

Document: 553633
ICSTT-RM405f-EN-P

Issue 07

Configuration Guide (AADvance Controller)


The slot and bus numbers must be the same as the actual physical position of the
installed modules. Therefore, for this example you would allocate I/O modules as

follows:

A 9401 module to the empty slot 1 on IO Bus 1

A 9451 module to the empty slot 2 on IO Bus 1.

Assign I/O Modules to I/O Bus Slots

If you are assigning a single module you can assign the module to any empty I/O bus

slot. If you are creating a redundant group you have to find two or three consecutive

empty slots and assign the module to the first empty slot in the group.

Note: If required, you can use the AADvance Workbench to move configured
modules to other slots to create a series of adjacent empty slots. Remember to move
the actual modules in the controller to the changed slots.

To assign an I/O module do the following:

1) Select the Equipment tab.
2) Expand the IO Bus 1.
3) At an empty slot right-click to select Insert IO. Move the cursor to the right to

select from the choice of available modules (empty slots position 16 - 24 shown in

bold).

Advertising