Connect a Slave Device, Half Duplex
You can use a half duplex serial connection to connect a single Modbus slave device to
the AADvance controller. To make the physical connection, do the following:
1) Select a suitable cable. We recommend 2-pair, overall shielded cable.
2) Remove the serial port connector from the 9100 processor base unit.
3) Make the connections shown in the illustration. Terminate the twisted pair with a
120
resistor in series with a 68nF capacitor at both ends.
4) Connect the signal ground (not illustrated) from the 0V terminal to the slave
device.
Note: Do not connect the signal ground to the AC safety ground.
5) Insert the connector into the 9100 processor base unit.