Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 85

Advertising
background image


Document: 553633
ICSTT-RM405f-EN-P
Issue 07

4-45

Processor Module A Ready

Direction: input to application from controller
Type: boolean
Values:

TRUE = The 9110 processor module in the given slot is synchronized (see

description)

FALSE = The processor module is out of synchronization or missing.

Description:
Reports that a processor module within a dual or triple modular redundant

configuration is present and is synchronized with one or both of its peers. Reports that
a simplex processor module is present.

Processor Module B Ready

Direction: input to application from controller
Type: boolean
Values:

TRUE = The 9110 processor module in the given slot is synchronized (see

description)

FALSE = The processor module is out of synchronization or missing.

Description:
Reports that a processor module within a dual or triple modular redundant

configuration is present and is synchronized with one or both of its peers. Reports that
a simplex processor module is present.

Processor Module C Ready

Direction: input to application from controller
Type: boolean
Values:

TRUE = The 9110 processor module in the given slot is synchronized (see

description)

FALSE = The processor module is out of synchronization or missing.

Description:
Reports that a processor module within a dual or triple modular redundant

configuration is present and is synchronized with one or both of its peers. Reports that

a simplex processor module is present.

Processor Module A NVRAM Battery Health

Direction: input to application from controller
Type: boolean
Values:

TRUE = The back-up battery in the 9110 processor module in the given slot is

present and its voltage is within acceptable limits.