Configuring digital inputs – Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 117

Advertising
background image


Document: 553633
ICSTT-RM405f-EN-P
Issue 07

5-19

Wire Variables to Analogue Output Channels

To wire variables to analogue output channels do the following:

1) Select a analogue output module on the I/O bus.

The module status variable <tagname> appears in the Variable field.

2) Select the channel that you want to wire to a variable.

3) Click the button next to the Channel Variable fields.
4) Choose a data structure from the three options displayed: Simple, Compact,

Full.

The Select Variables dialog box is displayed.

5) Select a named structure, click OK.
6) Repeat steps 2 to 5 for each channel.

Configuring Digital Inputs

You can wire digital input channels to the following variable type and data structures:

BOOL (the <variable_name> gives the input state)

T9K_DI_Compact (provides three elements)

T9K_DI_Full (six elements)

The structures provide additional information about the input, such as line fault status
and discrepancy status. You can also define custom thresholds for digital inputs.