Set the RSLogix UNICAST Configuration
The AADvance controller uses the Unicast mode for CIP You will need to configure
the Unicast option in the RSLogix CLX configuration.
Produced Variable
Select a CLX configuration Produced CIP variable.
Check the Allow Unicast Consumer Connections.
Consumed variable
For a Consumed Variable select a Consumed CIP variable.
1) Set the RPI value to 500.0 ms. (the default value is 20.0 ms).
2) Check the Use Unicast Connection over Ethernet IP.