Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 131

Advertising
background image


Document: 553633
ICSTT-RM405f-EN-P
Issue 07

5-33

AIM_HART_FULL_01.
ELAPSED

DINT Elapsed time in ms.

since last valid non
passthrough

communication

This element resets to zero whenever
fresh data is received. The data is
refreshed approximately every four

seconds for a small system. This rate
proportional to the system size and the
number of HART devices in use, so it

will be slower on larger systems. If
HART Passthrough is enabled then no

fresh data is received.

AIM_HART_FULL_01.
PASSTHROUGH

BOOL Passthrough

Communication
status

TRUE: Passthrough in progress

FALSE: Passthrough not in progress

Note: At least one CIP Produce variable must be defined. If there are no CIP

produce/consume variables the CIP stack does not get activated. Refer to the CIP
topics in this document on how to set up CIP produce/consume variables.

Configure HART for Field Device Monitoring

To configure the Analogue input Channels to monitor field devices that support the
HART protocol do the following:
1) Create HART variables within the Dictionary; set the type to T9K_AI_HART.
2) Go to the Equipment Tree View and select an Analogue Input or Analogue

Output module. Click on the HART tab.

The example below is an Analogue Input module.

3) Select a Channel, then click

.

4) Choose the T9K_AI_HART variable.
5) Wire this variable to each channel that has a HART device using a Tag name, click

OK.

6) Return to the Equipment Tree View, select a channel
7) Select the HART tab; put a tick in the box labeled Enable HART on this

Channel, click Apply