Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 207

Advertising
background image


Document: 553633
ICSTT-RM405f-EN-P
Issue 07

9-21

Configure a Modbus Master Object for Modbus RTU

Note: You have to create a Modbus Master object before you can carry out this task.

You have to configure the communications and control settings for a Modbus Master

object for Modbus RTU when you want to use the Modbus RTU protocol. Do the
following:

1) Select the Equipment tab on the Project tree view and then select the Modbus

master object you want to configure.

The editor for the Modbus master object opens.

2) Select the General tab.
3) Enter a suitable name for the Modbus master object, or accept the default. You

can use any combination of alphanumeric characters and punctuation, including

spaces.

4) Ensure that the Protocol is set to RTU (the default), click Apply.

The editor has three tabs; the tabs are named General, Broadcast and

Statistics.

The Workbench sets the Port Type to Serial.

The Workbench sets the Port Id to the first serial port on the associated

processor module.

5) Set the Port Id to match the identity of the serial port you will use for the link to

the Modbus slave(s).

6) Set the Timeout (in milliseconds) to suit the system, or accept the default value.

Note: We recommend the Timeout be set to a value less than 3,000ms.

7) Set the Message Wait Interval (in milliseconds) to suit the slave devices, or accept

the default value.

8) If you intend to use the control variable, set the Control Variable Address to the

Modbus address of the holding register; otherwise accept the default 0 to disable.

9) Similarly set the Status Variable Address.
10) Click Apply.