Document: 553633
ICSTT-RM405f-EN-P
Issue 07

4-51

RTC Program: Year

Direction: output from application to controller
Type: word
Values:

2,000 to 2,399

Default 0 (zero)

Description:
Specifies the year part of the date to be written to the real-time clock the next time

the RTC control variable RTC Write is asserted TRUE. The value will be written

only if the RTC control variable Year is TRUE.

RTC Program: Month

Direction: output from application to controller
Type: word
Values:

1 to 12

Default 0 (zero)

Description:

Specifies the number of the month part of the date to be written to the real-time clock
the next time the RTC control variable RTC Write is asserted TRUE. The value will

be written only if the RTC control variable Month is TRUE.

RTC Program: Day of Month

Direction: output from application to controller
Type: word
Values:

1 to 31

Default 0 (zero)

Description:
Specifies the day of the month part of the date to be written to the real-time clock the

next time the RTC control variable RTC Write is asserted TRUE. The value will be

written only if the RTC control variable Day is TRUE.