Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 212

Advertising
background image

9-26

Document: 553633
ICSTT-RM405f-EN-P

Issue 07

Configuration Guide (AADvance Controller)


Modbus Ping Mode, Interval and Address

The ping mode is specified individually for each slave; it defines the action the Modbus

master should take if the slave fails to respond after the specified number of retries.
The AADvance controller supports a Function Code 08 ping mode for Modbus RTU

slaves; choose this if the slave supports it because it is a short message. The Read

Holding Register mode is an alternative; choose this if the slave does not support
Function Code 08. The Modbus master will try to read a single register. Read

Holding Register is the only method available to ping a Modbus TCP slave. You can

also set a Do Not Ping setting for both protocols.
The ping address is for the Read Holding Register mode and is also specified

individually for each slave; it is the Modbus address of the holding register. It is not

used by the Function Code 08 mode.

Modbus Ping Mode Settings - RTU

To check the settings do the following:

Function Code 08 Ping Mode Setting

1) Select the Equipment tab on the Project tree and then a Modbus master object

that has been set up to run the RTU protocol.

Check this by selecting the General tab and that the Protocol row is set to
RTU.

2) Select the slave link associated with the master object.

The editor for the slave link opens.

3) Select the General tab.
4) Check that the Ping Mode has been set for Function Code 08.