The AADvance Workbench inserts a network into the Hardware Architecture
view.
4) Create a connection between a configuration and the newly inserted CIP network.
Note: You can only connect Series 9000 and Series 8000 configurations to a CIP
network. If you try to connect a CIP network to a configuration that does not
support CIP (for example, a T6210 system) then the AADvance Workbench
displays a warning, and the connection will not be made.
5) Select the CIP connection link then select the properties
The Connection – Properties dialog opens.
6) Enter the IP Address in the allocated to the AADvance controller for the CIP
network in the Value field for IPAddress1, click OK.
Note: The default IP Address for a connection between a configuration and a
CIP Network is blank. If you do not specify a valid IP Address here, the
AADvance Workbench will report an error at build time, ‘Network CIP: invalid
connection properties for … (the particular configuration).’
7) The CIP communications network on the AADvance controller is now defined.
Note: The AADvance Controller will support a maximum of 255 connections.
8) Now set up the RSLogix controller.