Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 125

Advertising
background image


Document: 553633
ICSTT-RM405f-EN-P
Issue 07

5-27

<tagname>.CNT

INT

Raw count

A count representing the current on the
channel in units of 1/256mA

0 represents 0mA; 5,120 represents 20mA

Accurate to within ± 13 counts, equivalent to
± 0.05mA

<tagname>.LF

BOOL

Line fault

TRUE: state (.STA) is 1, 5, 6 or 7

FALSE: state (.STA) is 2, 3 or 4

<tagname>.DIS

BOOL

Discrepancy

TRUE: there is a discrepancy in current
greater than 2% between the channels of two
or three modules in a redundant configuration

(†)

<tagname>.CF

BOOL

Channel fault

TRUE: module diagnostics detect a fault in the
channel electronics or firmware (state = 7)

<tagname>.STA

USINT

State

Reports a state value for the channel:

1 = open circuit
2 = transmitter fault (low)
3 = normal
4 = transmitter fault (high)
5 = short-circuit
6 = over range
7 = faulted

Note: (†) Discrepancy can only be reported TRUE when two or three modules are
active in a group.

Faulted State for Analogue Inputs

An analogue input channel is faulted (the state reports a value of 7) when the channel

is incapable of reporting a count within a safety accuracy specification of 1% of the full

scale measurement range of 5,120 (51 counts, 0.2mA).
When the state reports the value 7 then the following 'safe' values are reported by the

other variables:

Process Value = a calculated value based on a Count value of 0

Line Fault = TRUE

Discrepancy = TRUE

Channel Fault = TRUE

Count = 0