Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 221

Document: 553633
ICSTT-RM405f-EN-P
Issue 07
9-35
Table 30:
Modbus TCP Link Identification and Control Settings
Description
Value(s)
Default
Remarks
Unit Id
0 to 255
255
IP Address
0.0.0.0 to
255.255.255.255
0.0.0.0
TCP Port
1 to 65,535
502
TCP port 502 is suggested for
Modbus TCP devices (Modbus
specification version 1.1b)
Retries
0 to 10
3
Control Variable
Address
1 to 65,536,
or 0 to disable
0
The address of a control register (†)
0 = inactive
1 = standby
2 = active
Status Variable
Address
1 to 65,536,
or 0 to disable
0
The address of a status register (†)
0 = healthy
1 = initializing
2 = communications failure
3 = error
Slave Wait
Interval
0 to 65,535ms
50ms
Ping Mode
Do Not Ping;
Read Holding Register
Do Not Ping
Ping Interval
0 to 65,535ms
5,000ms
Ping Address
1 to 65,536,
or 0 to disable
0
Note: (†) The 'remarks' here summarize the values allowed for the contents of the
register.