Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 221

Advertising
background image


Document: 553633
ICSTT-RM405f-EN-P
Issue 07

9-35

Table 30:

Modbus TCP Link Identification and Control Settings

Description

Value(s)

Default

Remarks

Unit Id

0 to 255

255

IP Address

0.0.0.0 to
255.255.255.255

0.0.0.0

TCP Port

1 to 65,535

502

TCP port 502 is suggested for

Modbus TCP devices (Modbus
specification version 1.1b)

Retries

0 to 10

3

Control Variable

Address

1 to 65,536,

or 0 to disable

0

The address of a control register (†)

0 = inactive

1 = standby

2 = active

Status Variable

Address

1 to 65,536,

or 0 to disable

0

The address of a status register (†)

0 = healthy

1 = initializing

2 = communications failure

3 = error

Slave Wait
Interval

0 to 65,535ms

50ms

Ping Mode

Do Not Ping;

Read Holding Register

Do Not Ping

Ping Interval

0 to 65,535ms

5,000ms

Ping Address

1 to 65,536,
or 0 to disable

0

Note: (†) The 'remarks' here summarize the values allowed for the contents of the
register.