Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 126

Advertising
background image

5-28

Document: 553633
ICSTT-RM405f-EN-P

Issue 07

Configuration Guide (AADvance Controller)


HART

The AADvance controller supports utilizing dedicated HART modems on each
analogue input and output channel allowing HART field device status, diagnostics and

process data to be integrated into the application logic, thus increasing the level of SIF

diagnostics significantly.
The AADvance analogue input/output modules use HART commands #03 to collect

data from the field device as defined by Revision 5 of the HART specification. The

application can be configured to use HART information to monitor and respond to

device conditions. It may also be used to provide diagnostic information such as
comparison and error reporting.
An additional feature of the AADvance controller is that it t also combines with the

AADvance DTM to enable asset management software (ASM) to communicate with
HART devices.

Note: The AADvance system does not alter the messages passed between the asset
management software and the field device and acts as a transport mechanism only.

AADvance HART Features

Provides passthru support for HART Standards 5, 6 and 7.

Variables can be configured for each Analogue input and output channel to

monitor HART device information.

HART support is available on each Analogue Input or Output channel.