Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 142

Advertising
background image

5-44

Document: 553633
ICSTT-RM405f-EN-P

Issue 07

Configuration Guide (AADvance Controller)


Overcurrent Protection for Digital Outputs

The AADvance controller has three mechanisms to protect its digital output channels:

Inrush current protection

Short circuit protection for energized channels

Short circuit protection for de-energized channels

The controller tolerates inrush currents so that its digital outputs can energize
capacitive loads without causing the controller to report a short circuit. The

illustration shows the characteristics of the maximum load currents that the controller
will tolerate when a digital output is commanded on. If the load current enters the

region above the curve on the graph, the controller applies its inrush current

protection.

After allowing for inrush, the controller engages its short circuit protection for an

energized channel when the loop current reaches 2A.

Short circuit detection on an energized channel is immediate and the channel is de-

energized. The controller reports the condition until the short circuit is cleared.

When the short circuit is removed, the channel will re-energize. The short circuit

report is then cleared by pressing the fault reset button on the 9110 processor

module or by setting the commanded state is set to FALSE.

The controller checks de-energized digital output channels for potential short circuits.

Periodically, the controller partially turns on each de-energized output in turn and

measures the loop current. If the loop current shows a loop resistance of less than
approximately 10

, the controller reports a short circuit.

Advertising