Parameters for CIP Producer and Consumer Varaibles

Each production variable and consumption variable for CIP over Ethernet/IP

communications has a set of parameters as detailed in the tables.

Note: A maximum of 128 producer and 128 consumer variables can be defined.

Table 18:

Parameters for Production Variables

Description

Value(s)

Default

Remarks

Maximum number
of connections

1 to 10

5

The maximum number of simultaneous
consumers of the particular variable (†)

Note: (†) The AADvance controller rejects any CIP requests to connect to a

produced variable beyond the maximum number of connections (255). Do not set the
number of connections higher than necessary because each connection uses resources
from a limited pool.

Table 19:

Parameters for Consumption Variables

Description

Value(s)

Default

Remarks

Producer

A unique string

Can include spaces and

other punctuation
characters

None

A user-defined name for the producing device

labelled 'Device Name' in Producer List.

Path to Producer

A valid address for a

Logix controller

None

Labelled 'CIP Path to Device' in Producer List.

(refer to Configure an AADvance Variable as a
consumer)

Remote Tag Name A string

None

Specifies the name of the variable as it is known

to the Logix controller.

RPI (ms)

2 to 1,000

20 (‡)

Requested packet interval

Defines how frequently the Logix controller
should offer the variable to the AADvance

controller.

Note: (‡) The RPI should not be set below 200ms at the current release.