Direction: input to application from controller
Type: boolean
Values:

TRUE = power feed voltage is within specification (18 to 32V dc).

FALSE = power feed is outside specification.

Description:
Reports the health of power feed 1 (nominal 24V dc) to the 9110 processor module in

the given slot.

Processor Module A 24V2 Power Feed Health

Direction: input to application from controller
Type: boolean
Values:

TRUE = power feed voltage is within specification (18 to 32V dc).

FALSE = power feed is outside specification.

Description:

Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in

the given slot.

Processor Module B 24V2 Power Feed Health

Direction: input to application from controller
Type: boolean
Values:

TRUE = power feed voltage is within specification (18 to 32V dc).

FALSE = power feed is outside specification.

Description:

Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in
the given slot.

Processor Module C 24V2 Power Feed Health

Direction: input to application from controller
Type: boolean
Values:

TRUE = power feed voltage is within specification (18 to 32V dc).

FALSE = power feed is outside specification.

Description:
Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in

the given slot.