Document: 553633
ICSTT-RM405f-EN-P

Issue 07

Configuration Guide (AADvance Controller)


HART Passthrough

Direction: Appliction to the controller.
Type: BOOLEAN
Values:

TRUE = HART Passthrough is enabled and available for an Analogue Module.

FALSE = HART Passthrough is disabled and not available.

DEFAULT = FALSE

Description: Initiates the HART Passthrough feature to support HART messages on

the Analogue Input and Output Modules. The system will support messages on each
channel independently or in parallel

RTC Status Variables

The RTC status variables provide information about the controller real-time clock to

the application.

RTC Status: Year

Direction: input to application from controller
Type: word
Values:

2,000 to 2,399, or 0 (see description)

Description:
Reports the oldest value of real-time clock (RTC) year as voted by every 9110

processor module which is present and synchronized. Only updated if the real-time
clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will

be 0 (zero).

RTC Status: Month

Direction: input to application from controller
Type: word
Values:

1 to 12, or 0 (see description)

Description:
Reports the oldest value of real-time clock (RTC) month as voted by every 9110

processor module which is present and synchronized. Only updated if the real-time

clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will
be 0 (zero).