Configuration guide (aadvance controller) – Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 130

5-32
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Table 11:
T9K_AI_HART_FULL Data Structure
Identifier
Type Description
Remarks
AIM_HART_FULL_01.I REAL Current (mA)
AIM_HART_FULL_01.
V1
REAL Primary variable
AIM_HART_FULL_01.
U1
BYTE Primary variable units
code
AIM_HART_FULL_01.
V2
REAL Second variable
AIM_HART_FULL_01.
U2
BYTE Second variable units
code
AIM_HART_FULL_01.
V3
REAL Third variable
AIM_HART_FULL_01.
U3
BYTE Third variable units
code
AIM_HART_FULL_01.
V4
REAL Fourth variable
AIM_HART_FULL_01.
U4
BYTE Fourth variable units
code
AIM_HART_FULL_01.
COMMS
BOOL Communication
status
TRUE: Communication OK
FALSE: Communication stopped
AIM_HART_FULL_01.I
<tagname>.DEVICE
BYTE Device status
The device status byte mimics the
HART field device status. Appendix E
of the HART Application Guide gives
details.
Bit 7: field device malfunction
Bit 6: configuration changed
Bit 5: cold start
Bit 4: more status available
Bit 3: analogue output current fixed
Bit 2: analogue output saturated
Bit 1: non-primary variable out of limits
Bit 0: primary variable out of limits