Configuration Guide (AADvance Controller)


Table 11:

T9K_AI_HART_FULL Data Structure

Identifier

Type Description

Remarks

AIM_HART_FULL_01.I REAL Current (mA)

AIM_HART_FULL_01.
V1

REAL Primary variable

AIM_HART_FULL_01.

U1

BYTE Primary variable units

code

AIM_HART_FULL_01.
V2

REAL Second variable

AIM_HART_FULL_01.

U2

BYTE Second variable units

code

AIM_HART_FULL_01.
V3

REAL Third variable

AIM_HART_FULL_01.

U3

BYTE Third variable units

code

AIM_HART_FULL_01.
V4

REAL Fourth variable

AIM_HART_FULL_01.
U4

BYTE Fourth variable units

code

AIM_HART_FULL_01.
COMMS

BOOL Communication

status

TRUE: Communication OK

FALSE: Communication stopped

AIM_HART_FULL_01.I
<tagname>.DEVICE

BYTE Device status

The device status byte mimics the
HART field device status. Appendix E

of the HART Application Guide gives
details.

Bit 7: field device malfunction

Bit 6: configuration changed

Bit 5: cold start

Bit 4: more status available

Bit 3: analogue output current fixed

Bit 2: analogue output saturated

Bit 1: non-primary variable out of limits

Bit 0: primary variable out of limits