Configuration Guide (AADvance Controller)


SNCP_KVB_ERR_NO_PRODUCER

0x04

At the beginning of a connection or

following "BindRespTimeout" milliseconds
during data exchange.

SNCP_KVB_ERR_BAD_CRC

0x05

Producer and consumer binding tables

CRC mismatch during connection

SNCP_KVB_ERR_IMPOSSIBLE_TO_
BIND

0x06

Conversion of structures not supported on
hetrogeneous binding link

SNCP_KVB_ERR_IP_DENIED

0X07 Producer only error, indicates that a

consumer with an unknown/unexpected IP
Address is requesting a bindings link. The

link is denied.

SNCP_KVB_ERR_BAD_PRODUCER_
ID

0X08 Producer only error, indicates that the

producer has received a bindings link
request from a consumer and that request

does not contain the expected producer
identity. The link is denied.

SNCP_KVB_ERR_BAD_GROUP_ID

0X09 Producer only error, indicates that the

producer has received a bindings link
request from a consumer, and that request
does not contain a known bound variable

group identity. The link is denied.

SNCP_KVB_ERR_BAD_BUFF_SIZE

0X0A Producer only error, indicates that either

the producer or consumer does not have
sufficient buffer space to translate the

bound variables so that the link cannot be
established.

SNCP_ERR_BAD_CONFIG

0X0B Producer only error, indicates that the

producer is unable to obtain the consumers
IP address information from the network
configuration file. The link is denied.