Connect a Slave Device, Full Duplex

You can use a full duplex serial connection to connect a single Modbus slave device to

the AADvance controller. To make the physical connection, do the following:

1) Select a suitable cable. We recommend 3-pair, overall shielded cable.
2) Remove the serial port connector from the 9100 processor base unit.
3) Make the connections shown in the illustration. Terminate the twisted pairs with a

120

resistor in series with a 68nF capacitor at the receiver ends.

4) Connect the signal ground (not illustrated) from the 0V terminal to the slave

device.

Note: Do not connect the signal ground to the AC safety ground.

5) Insert the connector into the 9100 processor base unit.