Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 244

Advertising
background image

10-10

Document: 553633
ICSTT-RM405f-EN-P

Issue 07

Configuration Guide (AADvance Controller)


00

3) Select the Network tab and enter the values; the default recommended values:

Connect TimeOut = 1000

BindResp Timeout = 1200

MaxAge = 2500

BindReqTimeout = 1000

Update Timeout = 60000

Configure Bindings

You need to set up data links between resources to create binding variables. You can

link resources from the Internal Bindings List Window or set up a link between

resources from the Link Architecture view.
1) Select the Link Architecture View.
2) Select the data link button on Resource 1 and extend the data line to the data

link button on Resource 2.

3) Repeat this for Resource 2 to Resource 1.