Configuration Guide (AADvance Controller)


Write Holding
Registers

Input Registers;

Holding Registers

Holding
Registers

Controlling a Modbus Message

Every Modbus message that originates at a Modbus master (broadcast message or slave

link message) has provision for a control (a coil), which allows the application to

control whether or not the message should be sent. The coil is located at the address

that is specified by the message parameter named 'Control'. You can allocate the same
address (and coil) to multiple messages.
The use of a coil is optional. If you want to use a coil, you have to declare a variable

for it in the application Dictionary; and also specify the address in the memory map
of coil data.
If you do not specify an address then the message is always enabled. The variable in the

application Dictionary has the functions listed in the table.

Table 35:

Modbus Message Control Register

Value

Meaning

Description

0

Enabled

The message is enabled and, if the associated Modbus
object is enabled, the message is sent

1

Disabled

The message is disabled and is never sent

Configure Statistics for a Modbus Slave Link

Slave link statistics are available to the application. To use the statistics, do the
following:

1) Select the Equipment tab on the Project tree view and then select the slave link

you want to configure.

The editor for the slave link opens.

2) Select the Statistics tab.

The editor shows three fields.