4) Click Browse to select the location of the installation or Next to choose the
default location.
5) Click Next to confirm the installation.
ControlFLASH installs and shows the progress bar.
6) Click Yes I want to launch ControlFLASH, then click Close.
Upgrade Processor OS, FPGAFPGA, LSP and BUSP Firmware
This procedure describes how to upgrade the processor module firmware using
ControlFLASH.
Note: ControlFLASH can upgrade 3 processor modules at once when installed into a
9100 base unit.
WARNING
FIRMWARE UPGRADE DANGER TO A RUNNING SYSTEM
Do not attempt to upgrade firmware on a running system. Control
FLASH will not warn you that a system is running and you will lose
control of the application when the system reboots.
1) Run the ControlFLASH software by either:
Launching from the installation
Double clicking the desktop icon
Launching from the Start button
2) Click Next.
3) Select T9110 from the list.