Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 218
![background image](/manuals/580880/218/background.png)
9-32
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Configure Statistics for a Modbus Master Object
Modbus master statistics are available to the application. To use the statistics, do the
following:
1) Select the Equipment tab on the Project tree view and then select the Modbus
master object you want to configure.
The editor for the Modbus master object opens.
2) Select the Statistics tab.
The editor shows three fields.
The default values disable the statistics reporting.
3) Set the Reporting Mode.
4) Set the Data Variable Address to the Modbus address of the holding register.
5) Similarly set the Reset Variable Address.
6) Click Apply.
Modbus Statistics Parameters
Each Modbus message has a series of parameters as detailed in the table.
Table 28:
Modbus Slave Link Message Parameters