Refresh Timeout - Enter a value in the range 1 to 10000ms. This is the
maximum number of milliseconds allowed between successive refreshes of

input data before the data is declared invalid. Should the time be exceed and

the data declared invalid the input data will either retain the last received value
or revert to a fail-safe condition according to the Hold Last Valid Value setting.
The Refresh Timeout should be set to the longest delay before a fail-safe

action should be taken. This will be the Process Safety Time for the input data.
The corresponding Output board has a Refresh Interval parameter; this

controls how often data is sent to the Input board. The Refresh Interval

should be calculated to deliver at least two updates within the Refresh

Timeout, under worst case conditions. A Refresh Timeout which is too
short for the network size and complexity will make it impossible to deliver

fresh data often enough.

Value in Failed State - Enter a value in the range -9.999999e+38 to
+9.999999e+38. This sets the control value to be adopted by the inputs when

the input has not been refreshed within Refresh Timeout and is therefore

declared invalid. Where the input corresponds to an integer the fractional part
if truncated. The value is always adopted at application start-up, though it will

not be used while the Hold Last Valid Value variable is TRUE.

The screen view below shows the configuration of a 16 channel analogue input board.

The board being configured is for Peer Network 4, source peer is Peer 4 and the
data block identity Board 3.