Configure the I/O Module Process Safety Time

When you configure the process safety time for an I/O module, you can choose to

inherit the top-level value set for the processor or specify a value for the I/O module.
To define the I/O module process safety time do the following:

1) Select a module from the I/O Bus.
2) Put a tick in the Inherit box to inherit the top-level Process Safety Time; or
3) De-select the Inherit box and enter a value into the Process Safety Time field.

Wire Status Variables to I/O Modules

You can wire a variable to an I/O module so the application can receive status
information from the module. The AADvance Workbench provides a structure

(T9K_TA_GROUP_STATUS) for module status information. To wire a status

variable to an I/O module do the following:

1) Declare a variable in Dictionary. Use the type T9K_TA_GROUP_STATUS and

make sure that the direction is set to input.

2) Select a module from the I/O bus.

The unwired term appears in the Variable field.

3) Click the button adjacent to the Variable field.