Peer-to-peer controller setting summary – Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 267

Advertising
background image


Document: 553633
ICSTT-RM405f-EN-P
Issue 07

11-19

Peer-to-Peer Controller Setting Summary

You should follow the process described in this chapter.
The network configuration is as follows:

16 analogue outputs are sent from Controller 1 to Controller 2

16 analogue values are sent form controller 1 to Controller 3

16 digital values are sent from Controller 2 to controller 4

Table 37:

Controller 1 - Dual Peer-to-Peer Net Control, Network 1, Subnet 1

Value

Comment

DXPNC40

Network Interface

A

Network connected to processor A

Network Identity

1

Network 1

Subnet Identity

1

Subnet 1

Peer ID

1

Identity of this controller

Response Timeout

0

Default

Refresh Timeout

2000

Default

Slave Transmit timeout

500

Default

Enable Controller

TRUE

Enable Peer on this subnet

Master/Slave

FALSE

This is a slave connection

Peer List

Peer 1

10.10.1.1

Controller 1, network 1, subnet 1

Peer 2

10.10.1.2

Controller 2, network 1, subnet 1

Peer 3

10.10.1.3

Controller 3, network 1, subnet 1

Peer 4

10.10.1.4

Controller 4, network 1, subnet 1

Peer 5

Peer 6

Peer 7

Table 38:

Controller 1 - Dual Peer-to-Peer Net control, network 1 subnet 2

Value

Comment

DXPNC40

Network Interface

B

Network connected to processor B

Network Identity

1

Network 1

Subnet Identity

2

Subnet 1

Advertising