Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 263

Advertising
background image


Document: 553633
ICSTT-RM405f-EN-P
Issue 07

11-15

Wire the Analogue Output Channel Variables

Analogue output channels send analogue data to the corresponding analogue input
channels on the peer network.

1) Select the Data Variables tab.
2) Select a Channel row.
3) Select the R check box to set the variable data type,

not checked = DINT

checked = REAL.

4) Select the W button to connect to a variable.
5) If you need to disconnect a variable select U button.