Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 141

Document: 553633
ICSTT-RM405f-EN-P
Issue 07
5-43
The State Variable for Digital Outputs
The state variable for a digital output is an unsigned integer with a value from 1 to 7
representing the following:
1 = no-vfield: the field supply voltage is at or below 18V dc for that channel.
Note: When the state variable is 1, the field voltage (<tagname.V>) is reported as
0mV.
2 = de-energized: the commanded state is FALSE and the channel is de-energized.
3 = no-load: the controller cannot detect a load connected to the channel field wiring,
or the load is below the minimum required channel load of 10mA when commanded
TRUE.
4 = energized: the commanded state is TRUE and the channel is energized.
5 = short-circuit: the controller has detected a short-circuit condition, irrespective of
the channel drive state.
6 = field fault: an external source is driving the channel to an energized state or a
voltage greater than 18V dc, irrespective of the channel drive state.
7 = faulted.