Faulted State for Digital Outputs

A digital output channel is faulted (the state reports a value of 7) when normal

operation or diagnostics tests have identified a specific fault condition. A single
identified fault condition thus results in a state value of 7.
When the state reports the value 7 then the following 'safe' values are reported by the

other variables:

Line Fault = TRUE

Discrepancy = TRUE

Channel Fault = TRUE

Voltage = 0mV

Current = 0mA

Configure Advanced Channel Settings for Digital Outputs

The AADvance Workbench provides advanced settings for individual digital output
channels:

You can specify a shutdown state for an output; this defines how the output will

behave when its parent 9451 digital output module is in a shutdown mode.

You can disable the line test feature for an output; this disables detection of a no-

load condition.

To configure the advanced channel settings do the following:

1) Select a slot with a digital output module.

The module status variable name <tagname> that you assigned appears in the

Variable field.

2) Select Channel 01 and click the Advanced tab.

The 9451 Advanced Channel Settings dialog box opens.

3) Put a tick in the box labelled Use Custom Advanced Channel Settings.
4) Select the Shutdown State row and then select an option from the pull down list