Configuration Guide (AADvance Controller)


Value

Meaning

Description

0

Inactive

Disables the slave link

Slave is neither polled or pinged

1

Standby

Forces the slave link to operate in its standby mode

Modbus master continues to ping the slave to make
sure that communications are possible

2

Active

Forces the slave link to operate in its active mode

Slave is being polled for data

Note: If the application sets the register to any other value, the slave link is disabled.

Modbus Slave Link Status Register

The status register is an unsigned integer value (UINT) that is returned by the Modbus

driver to allow the application to monitor and act on faults. If you do not specify a

status register address, then the slave link does not report its status information to the
application. The variable in the application Dictionary has the values listed in the table.

Table 32:

Modbus Slave Status Register

Value

Meaning

Description

0

Healthy

Slave is operating normally

Link is active, no errors reported

1

Initializing/unavailable

The slave link is initializing

This value is also reported if the slave device has failed
to respond to a ping on a link declared as standby; if
the Modbus master is in error; or if the Modbus

master is set to inactive

2

Communications failure Slave is being polled for data and is not responding

3

Error/exception

The last message to the slave resulted in an exception
response

Note: The status value may toggle between 0 and one of the other values because as
soon as a good response is received then the status is set to the healthy value.