Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 152

Advertising
background image

5-54

Document: 553633
ICSTT-RM405f-EN-P

Issue 07

Configuration Guide (AADvance Controller)


1) Select the slot with the analogue output module.

The module status variable name <tagname> that you assigned appears in the
Variable field.

2) Select the channel to configure and click the Advanced tab.

The 9481/9482 Advanced Channel Settings dialog box opens.

3) Put a tick in the box labelled Use Custom Advanced Channel Settings.
4) Choose the advanced channel settings from the options.

Analogue Output Advanced Channel Settings

Each output channel from the 9481/9482 analogue output module supports the set of
control parameters detailed in the table.

Table 17:

Analogue Output Control Parameters

Description

Value(s)

Default

Remarks

Shutdown State

Off, Hold Last State,

Custom

Off

'Off' de-energizes the output during

a shutdown

'Hold Last State' forces the output
to remain in its last commanded
current, during a shutdown

'Custom' forces the output to go to

the value set in 'Custom Shutdown
Value', during a shutdown

Custom Shutdown
Value

As scaled range of
command value CV

-25

Output set when 'Shutdown State'
is set to 'Custom', during a

shutdown

Fail-Safe Guard
Band

0-100% of full scale
20mA (1% = 0.2mA)

1%

Threshold for discrepancy alarm
between command value CV and

Count CNT. A discrepancy alarm is
reported on parameter DIS.