Configuration Guide (AADvance Controller)
1) Select the slot with the analogue output module.
The module status variable name <tagname> that you assigned appears in the
Variable field.
2) Select the channel to configure and click the Advanced tab.
The 9481/9482 Advanced Channel Settings dialog box opens.
3) Put a tick in the box labelled Use Custom Advanced Channel Settings.
4) Choose the advanced channel settings from the options.
Analogue Output Advanced Channel Settings
Each output channel from the 9481/9482 analogue output module supports the set of
control parameters detailed in the table.
Table 17:
Analogue Output Control Parameters
Description
Value(s)
Default
Remarks
Shutdown State
Off, Hold Last State,
Custom
Off
'Off' de-energizes the output during
a shutdown
'Hold Last State' forces the output
to remain in its last commanded
current, during a shutdown
'Custom' forces the output to go to
the value set in 'Custom Shutdown
Value', during a shutdown
Custom Shutdown
Value
As scaled range of
command value CV
-25
Output set when 'Shutdown State'
is set to 'Custom', during a
shutdown
Fail-Safe Guard
Band
0-100% of full scale
20mA (1% = 0.2mA)
1%
Threshold for discrepancy alarm
between command value CV and
Count CNT. A discrepancy alarm is
reported on parameter DIS.