2) Select a slave link associated with a master object set to the TCP protocol.

The editor slave link opens.

3) Check that the Ping Mode has been set to Do Not Ping.

Restart a Link When No Ping Mode is Set

When a slave module fails the master stops sending messages to it except for the ping

message (if one is configured). If the failed slave module later becomes "Healthy" the

master will automatically detect this change because the module will respond to the
ping messages, the master will then start sending messages to it again.
However, when a slave module configured with Do Not Ping fails and later becomes

"Healthy" the master cannot detect this change because it is not sending any ping
messages to it. To resolve this stiuation the slave module must be restarted using

either the slave or the master control register. This can be done by the application or

by using the AADvance Workbench in debug mode.