TROUBLESHOOTING

1-193

August 9, 2005

D SERIES CONTROLLER

TROUBLESHOOTING AND COMPONENT REPLACEMENT

Ka a a

w s k

ERROR CODE P2064

[FDD] No space available.

Floppy disk has less than 12 KB of free space and the data cannot be saved.

Insert a floppy disk with sufficient free space and re-execute.

Delete unnecessary data from the floppy disk and re-execute.

_____________________________________________________________________

ERROR CODE P2065

[Multi Disks] Invalid disk was loaded.

When loading data that is saved to several floppy disks, the data on the currently in-
serted floppy disk does not follow the data previously loaded.

Use a PC to verify data on disk.

Ensure data is loaded in the order it is saved.

_____________________________________________________________________

ERROR CODE P2066

Boot flash state is write-disenable.

Attempting to rewrite the contents of the boot flash memory.
Example: Rewriting the MAC address.

Boot flash memory is write-protected

.

_____________________________________________________________________

ERROR CODE P2067

[Serial Flash] File directory error.

Specified directory exists, but cannot be read due to abnormality.
Example: Error when accessing the serial flash memory.

Replace the serial flash memory on the 1KA board.

_____________________________________________________________________

ERROR CODE P2068

Cannot execute program being edited now.

An attempt is made, from another monitor, to edit the file currently being edited, or to
CALL the program from another program.

Complete the program edit and re-execute.

_____________________________________________________________________