TROUBLESHOOTING

1-35

August 9, 2005

D SERIES CONTROLLER

TROUBLESHOOTING AND COMPONENT REPLACEMENT

Ka a a

w s k

ERROR CODE D1507

AC primary power OFF.

This error occurs when there is an instantaneous decrease in the primary power to the
AVR for control power supply (130–145 VAC or less for 20–30 msec).

Mother Board

1KP board

1KB board

1KX board

EPLD

AVR

output

cut

AVR for

control power

Main

disconnect

Primary

power

Control

power

210 VAC

AC error

signal

REMOTE

Local

bus

F1

T1

F3

1KQ/1NQ board

Transformer

Circuit

breaker

Main causes include:
1. The primary power is below the specified rating, or an instantaneous power decrease

occurred.

2. The non-fuseable breaker (NFB) F1 for the control power supply is turned OFF or

tripped due to a short-circuit.

3. An instantaneous decrease in the 210 VAC supply to AVR for the control power

supply.

4. Circuit breaker F3 is OFF or tripped due to a short circuit.
5. Defective AVR.
6. Defect in the primary power supply.
7. Defective 1KP board.
8. Defective 1KQ/1NQ board.

It is normal for this error to occur when NFB F1 is set OFF and back ON.

Check power supply circuit through NFB F1 and repair as necessary.

Check power supply circuit to the AVR through the circuit breaker F3 and repair as
necessary.

Confirm that primary power is supplied according to specifications.

Replace the 1KP board.

Replace the 1KQ/1NQ board.

Replace the AVR.