TROUBLESHOOTING

1-37

August 9, 2005

D SERIES CONTROLLER

TROUBLESHOOTING AND COMPONENT REPLACEMENT

Ka a a

w s k

ERROR CODE D1509

Primary power source is too high.

Voltage level of the AVR for the control power supply is too high (267-277 VAC or more
for 1-2 sec.).

Mother Board

1KP board

1KX board

EPLD

AVR

output

cut

AVR for

control power

Main

disconnect

Primary

power

Control

power

210 VAC

AC error

signal

Local

bus

F1

T1

F3

1KQ/1NQ board

Transformer

Circuit

breaker

REMOTE

Main causes include:
1. Primary power exceeds the specified rating.
2. Defective AVR.
3. Defective 1KP power sequence board.
4. Defective 1KQ/1NQ relay board.
5. Power supply circuit problem.

Ensure the power supply to the controller is within ratings.

Check power supply circuit to the AVR.

Confirm the supply power is within specifications.

Replace the 1KP board.

Replace the 1KQ/1NQ board.

Replace the AVR.