TROUBLESHOOTING

D SERIES CONTROLLER

TROUBLESHOOTING AND COMPONENT REPLACEMENT

1-42

August 9, 2005

Ka a a

w s k

ERROR CODE D1514

I/O 24V fuse is open.

Fuse F2 on the 1KP board is open.

Main causes include:
1. Solenoid valve or diode polarity reversed.
2. Current load on the 24 VDC I/O circuit exceeds rating.
3. Short-circuit or ground fault in the 24 VDC I/O harness.
4. Defective 1KP board.

Check components for proper polarity and repair as necessary

.

Ensure the load on the 24 VDC I/O circuit is within rating.

Check the I/O harness and replace as necessary.

Replace fuse F2 on the 1KP board (after cheching for short-circuit).

If the above steps do not correct the problem, replace the 1KP board.

_____________________________________________________________________

ERROR CODE D1515

Mismatch in setting of safety circuit as single/double.

Main causes include:
1. Safety circuit setting between the software and hardware do not match.
2. Defective 1KP board.

Set SW-2 on the 1KP board to ON for a double circuit or OFF for a single circuit

.

In AUX 2021-2 set [2 Line] ON or [1 Line] OFF.

Replace 1KP board.

_____________________________________________________________________

ERROR CODE D1516

Mismatch betw hard/software settings for HOLD backup
time.

Main causes include:
1. The setting that specifies a two second delay before motor power is set OFF when

the RUN/HOLD switch is switched from RUN to HOLD, is not matched between the
software and hardware.

2. Defective 1KP board.

Set SW-1 on the 1KP board to ON for two second delay or OFF no delay

.

In AUX 2021-2 set the delay parameter to [standard] (delay) or [Off] (no delay).

Replace 1KP board.

_____________________________________________________________________