TROUBLESHOOTING

D SERIES CONTROLLER

TROUBLESHOOTING AND COMPONENT REPLACEMENT

1-58

August 9, 2005

Ka a a

w s k

ERROR CODE D4502

FIELD-BUS-INIT) Error Reply. XX

At fieldbus start-up, a mismatch in length of I/O data with the node at the end of the
connection is detected when a message is sent to the fieldbus I/F card, or maximum
I/O data length is exceeded.

Check the I/F card LED display. Match the I/O data length with the master

.

Ensure I/O data length is within length specified for the fieldbus I/F card.

Cycle controller power OFF and ON.

Replace fieldbus cable.

If this error recurs, contact KRI Customer Service (include sub-code XX)

.

_____________________________________________________________________

ERROR CODE D4503

FIELD-BUS-INIT) Reply timeout XX.

At fieldbus start-up, no response is detected due to defective hardware or incorrect
settings during I/F board initialization.

Check the I/F card LED display

.

Ensure the master and slave I/O data length match.

Cycle controller power OFF and ON.

Replace the fieldbus cable.

If this error recurs, contact KRI Customer Service (include sub-code XX)

.

_____________________________________________________________________

ERROR CODE D4504

ANYBUS) OUT/FB.CTRL request timeout. XX

Reading input signal area access is requested but denied due to hardware problem.

Check the I/F card LED display and reset the error

.

If this error cannot be reset, contact KRI Customer Service (include sub-code XX).