Omron SYSMAC CJ1W-EIP21 User Manual

Page 103

Advertising
background image

77

CIO Area Allocations

Section 4-2

Communications
Status 1
(EtherNet/IP Unit to
CPU Unit) (n + 12)

Word n+12 contains status flags related to the tag data links, as shown in the
following diagram.

15

Error Log Stored

ON

Unit

Indicates that an error record
is registered in the error log.

OFF

Unit

Indicates that no error records
are registered in the error log.
Also turned OFF when an
error log clear request is
received.

Bit

Name

Status

Manipulated

by

Unit operation

Bit

Name

Status

Manipulated

by

Unit operation

0

Verification Error

ON

Unit

Indicates that the information
registered for a target node in
the tag data link parameters is
different from the actual node
information.

Main causes:

• The specified target does not

exist.

• The variable name does not

match.

• The connection size is differ-

ent.

• Connection resources are

insufficient.

OFF

Unit

Indicates that a verification
error has not occurred. Also
turned OFF when a verifica-
tion error is cleared.

1

(Not used)

---

---

---

2

Tag Data Link Error ON

Unit

Indicates that there were two
or more errors in a connection
as an originator.

This status does not indicate
the following errors.

• Connection as a target
• Connection timeout due to a

Link OFF Error with the
switching hub

OFF

Unit

Indicates that the errors listed
above did not occur.

3

(Not used)

---

---

---

n+12

Tag Data Link Error

Invalid Communications Parameter

All Tag Data Links Operating

Verification Error

Tag Refresh Error

Tag Data Links Operating

Tag Database Error