364

Error Log Function

Section 14-4

14-4 Error Log Function

Errors detected by the EtherNet/IP Unit or built-in EtherNet/IP port are stored
in the error log along with the date and time of their occurrence. The error log
can be read and cleared from the Network Configurator.

Some error log records are cleared when the CPU Unit’s power goes OFF,
and other records are not cleared.

14-4-1 Error Log Data Specifications

Each error is recorded as one record in the error log.

Structure of Each Record

14-4-2 Error Log Registration

Error Log Storage Area

When an error occurs, information on the error and the time stamp are stored
in the Unit’s internal RAM as an error log record. Serious errors are recorded
in non-volatile EEPROM as well as RAM. The time read from the CPU Unit
during cyclic servicing is used for the time stamp.

The error log records stored in EEPROM are copied to RAM when the Unit
starts operating, so these records are retained even when the Unit’s power is
turned OFF or the Unit is restarted.

When the error log is read, the error log records in RAM are read. When the
error log is cleared, the error log records in both RAM and EEPROM are
erased.

Error Log Overflows

The error log can record up to 64 records. If another error occurs when the log
is full, the oldest record will be erased to make room for the new error record.

Power Interruptions when
Saving to EEPROM

If the power supply is interrupted or the Unit is restarted while the error log is
being written to EEPROM, the error log may be corrupted. When the Unit
starts, it performs a checksum test on the error log data read from EEPROM
to detect corrupted data.

14-4-3 FINS Commands for Error Logs

The following FINS commands can be sent to the EtherNet/IP Unit or built-in
EtherNet/IP port to read or clear the error log.

For details, refer to Appendix E FINS Commands Addressed to EtherNet/IP
Units or Built-in EtherNet/IP Ports
.

Item

Specifications

Record length

10 bytes/record

Number of records

64 records max.

Data type

Binary (time information: BCD)

Bit 15

Bit 00

Error code

Detail code

Minutes

Seconds

Day of month

Hour

Year

Month

Command code

Function name

MRC

SRC

21

02

ERROR LOG READ

03

ERROR LOG CLEAR

Advertising