89

Auxiliary Area Data

Section 4-5

4-5-2

Read/Write Bits (User Settings)

A417

A41700 to
A41715

CPU Bus Unit Error,
Unit Number Flags

When an error occurs in a data exchange between
the CPU Unit and a CPU Bus Unit, the CPU Bus
Unit Error Flag (A40207) and the corresponding flag
in A417 are turned ON. Bits 00 to 15 correspond to
unit numbers 0 to F.

The ERR/ALM indicator on the front of the CPU Unit
will flash, but CPU operation will continue.

0: No error

1: Error

A427

A42700 to
A42715

CPU Bus Unit Set-
ting Error, Unit
Number Flags

When a CPU Bus Unit Setting Error occurs, A40203
and the corresponding flag in A27 are turned ON.
Bits 00 to 15 correspond to unit numbers 0 to F.

The ERR/ALM indicator on the front of the CPU Unit
will flash, but CPU operation will continue.

0: No setting error

1: Setting error

Word

Bits

Name

Description

Settings

A501

A50100 to
A50115

CPU Bus Unit
Restart Bits

Bits A50100 through A50115 can be turned ON to
reset CPU Bus Units number #0 through #15,
respectively.

Note The CPU Bus Unit Initializing Flags (A30200

to A30215) will turn ON when initialization of
the Units begins and turn OFF when it is com-
pleted.

Note When turning ON the CPU Bus Unit Restart

Bit from a ladder program, use the SET
instruction.

OFF to ON:
Unit restarted.

Automatically turned
OFF by system after
restart processing
has been completed.

Word(s)

Bit(s)

Name

Function