Using the LED Indicators and Display for Troubleshooting

Section 14-2

Ethernet Information Tab
Page

The Ethernet Information Tab Page shows the communications status at the
communications driver level. The error counter information can be used to
confirm whether communications problems have occurred. The tag data link
information can be used to confirm characteristics such as the bandwidth
usage (pps).

14-2 Using the LED Indicators and Display for Troubleshooting

14-2-1 Errors Occurring at the EtherNet/IP Unit or Built-in EtherNet/IP

Port

Errors Related to CPU Unit
Data Exchange

The 7-segment display alternates between the node address and error code.

Indicator

Error

Cause

Unit operation (Flag

status)

Error

log

(hex)

Countermeasure

MS

NS

7-segment

Flashing
red

Not lit

H1

Duplicate unit
number

The same unit
number is set on
another Unit.

Operation stops.

---

Set the unit num-
bers correctly and
restart the Ether-
Net/IP Unit or built-
in EtherNet/IP port.

Flashing
red

Not lit

H2

CPU Unit
faulty

---

Operation stops.

---

Replace the CPU
Unit if the error
recurs when the
CPU Unit is
restarted.