Omron SYSMAC CJ1W-EIP21 User Manual

Page 342

Advertising
background image

316

Using File Memory

Section 11-7

File Names Handled by CPU Unit

The files described in the following table can be read or written by the CPU
Unit.

Note

1.

Refer to information on file memory in the CS/CJ-series Programmable
Controllers Operation Manual
(W339).

2.

All files transferred automatically at startup must have the name AUTOEX-
EC.

File type

File name

Extension

Contents

Description

Data file

********

.IOM

Specified ranges of
I/O Memory

• Contains word (16-bit) data from a starting

word through an end word in one memory
area.

• The following areas can be used: CIO, HR,

WR, AR, DM, and EM.

Program file

********

.OBJ

Complete user pro-
gram

• Contains all the programs for cyclic tasks

and interrupt tasks, as well as task infor-
mation for one CPU Unit.

Parameter area file

********

.STD

• PLC Setup
• Registered I/O

tables

• Routing tables
• CPU Bus Unit

Setup and other
setup data

• Contains all of the parameter data for one

CPU Unit.

• There is no need for the user to distinguish

the various types of data contained in the
file.

• The file can be automatically read to or

written from the CPU Unit simply by speci-
fying the extension (.STD)

Files
trans-
ferred at
startup

Data files

AUTOEXEC

.IOM

I/O Memory data for
the specified number
of words starting from
D20000

• There does not necessarily need to be a

data file in the Memory Card when the
automatic file transfer function is used at
startup.

• The AUTOEXEC.IOM file always contains

DM Area data starting at D20000.

• All data in the file will be transferred to

memory starting at D20000 at startup.

Program
files

AUTOEXEC

.OBJ

Complete user pro-
gram

• There must be a program file in the Mem-

ory Card when the automatic file transfer
function is used at startup.

• Contains all the programs for cyclic tasks

and interrupt tasks, as well as task infor-
mation for one CPU Unit.

Parameter
area file

AUTOEXEC

.STD

• PLC Setup
• Registered I/O

tables

• Routing tables
• CPU Bus Unit

Setup and other
setup data

• There must be a parameter file in the

Memory Card when the automatic file
transfer function is used at startup.

• Contains all of the parameter data for one

CPU Unit.

• There is no need for the user to distinguish

the various types of data contained in the
file.

• All parameters in the file will be automati-

cally transferred to specified locations in
memory at startup.

Advertising