Omron SYSMAC CJ1W-EIP21 User Manual

Page 90

Advertising
background image

64

Other Parameters

Section 3-10

Using SNMP

Using SNMP Trap

Tab Page in Edit

Parameters Dialog Box

Setting

Function

SNMP

Not use SNMP service or

Use SNMP service

Specifies whether to use the SNMP.

If not using the SNMP service is specified, an SNMP manager will
not be able to connected from an external device.

SNMP Port

Sets the port number to use when connecting from an SNMP man-
ager.

It is normally not necessary to change this setting.

SNMP Contact Informa-
tion

Specifies the contact information as text.

This information can be read from the SNMP manager.

SNMP Location Informa-
tion

Specifies the location information as text.

This information can be read from the SNMP manager.

Authentication Check 1/2

Specifies the SNMP managers that can access the PLC.

To restrict access to only specific SNMP managers, specify the
SNMP managers using IP addresses or host names. Community
names can also be specified (e.g., public).

Ether one or two settings can be made.

Tab Page in Edit

Parameters Dialog Box

Setting

Function

SNMP Trap

Not use SNMP Trap ser-
vice or

Use SNMP Trap service

Specifies whether to use the SNMP trap.

If not using the SNMP trap service is specified, SNMP traps cannot
be sent to the SNMP manager.

SNMP Trap Port

Sets the port number to use to connect to the SNMP manager.

It is normally not necessary to change this setting.

Trap 1/2

Sets the SNMP manager destinations for SNMP traps.

The SNMP managers can be specified using IP addresses or host
names. Community names can also be specified (e.g., public).

Either one or two trap destinations can be set.