Automatic Clock Adjustment Switch

Section 12-3

12-3 Automatic Clock Adjustment Switch

The Automatic Clock Adjustment Switch is allocated in the CIO Area as
shown below. The first word n of the CIO Area is calculated using the following
equation.

n = CIO 1500 + (25

×

unit number)

Automatic Clock
Adjustment Switch
(Bit 05 of n)

The Unit control bit is shown in the following diagram.

When the Automatic Clock Adjustment Switch turns from OFF to ON, the Eth-
erNet/IP Unit or built-in EtherNet/IP port obtains the clock data from the SNTP
server on the network, and applies it to the local CPU Unit. After applying the
data, the switch automatically turns OFF again.

12-4 Automatic Clock Adjustment Error Processing

12-4-1 Automatic Clock Adjustment (SNTP) Errors

The following table shows the main causes and remedies for errors that occur
in the automatic clock adjustment function (SNTP).

12-4-2 Error Log Error Codes for the Automatic Clock Adjustment

Function

When an error occurs while the EtherNet/IP Unit or built-in EtherNet/IP port is
operating, the error code, detailed error code, and time the error occurred are
saved in the error log. The following table provides a list of the error codes.

Retry timer

Set the time to elapse before retrying when a connec-
tion to the SNTP server fails. This setting does not
normally need to be changed.

0
(10 s)

Adjust Time

This sets in the CPU Unit's clock data the time differ-
ence made up from the SNTP server's clock data.

To use the clock data from the SNTP server just as it
is, input 0.

+0:0

Item

Contents

Default

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

n

Automatic Clock
Adjustment Switch

Cause

Correction

SNTP, DNS server address not set

Reset each server address (IP address or
host name).

SNTP, DNS server communications time-
out

Inspect the communications path (Ether-
Net/IP Unit or built-in EtherNet/IP port,
cable connections, hub, router, server),
and correct the situation that is causing
the error.

CPU Unit internal clock could not be set

The automatic clock adjustment function
is not supported by certain CPU Units
(models, lot numbers) if they are in RUN
or MONITOR mode.